Online UPS System
- Liebert GXT-MT+ Features a comprehensive specification, satisfies safety criteria and electro magnetic compatibility standards, and offers intelligent monitoring and network management functions.
- Liebert GXT-MT+ Satisfies your requirements for high reliability and high availability of the AC power supply.
- Liebert GXT-MT+ Making easily deployed in an office & Small/Medium industrial application.
- Liebert GXT-MT+ Long run model (L) deploys adaptive battery architecture to maximise your valuable rack space utilisation. Application spcific battery configuration and placement ensures optimal performance with adequate power backup.
Note
- Liebert GXT-MT + Standard model is provided complete with internal battery.
- Liebert GXT-MT + (Long back up model) application specific battery and cabinet available through your local Emerson Network Power representative.
Applications
- Small Size Data Center.
- Telecommunication, VoIP.
- Small Office Network.
- Data Warehouses.
- Process Automation Equipment.
Features
- 0.8 output power factor.
- Emergency power off (EPO) (ECO mode).
- LCD display for status/faulst information.
- Configurable to energy saving mode (ECO).
- Extended Runtime Capabilities.
- Flexible (Site Specific) Battery Configuration.
- Compact Tower Design.
- Generator Compatible with wide input frequency range (40 to 70 Hz).
- Ultra wide input voltage range.
- High capacity Battery Charger for long backup.
- High input power factor & low THDi.
Flexible Configuration
- Extended Run time ready facilitated through a simple process of building up additional battery resources.
- Multiple AC output interfaces via IEC standard sockets with Programmable output.
Convenient Maintenance
- Fault type is clearly displayed for fast troubleshooting.
- LCD display provides maximum operational convenience when managing the UPS.
Intelligent Management Functions
- Stronger Battery charger on the GXT L model for quick recharge.
- Remote Monitoring is available through USB/RS232, and optional via dry contacts and SNMP. The monitoring option software supports TCP/IP with event log and analysis function.
- Self-diagnosis and protection enable the auto shutdown of the client terminal or server under abnormal mains supply or when battery is over discharge.
Technical Specification
|
Model
|
1 kVA
|
2 kVA
|
3 kVA
|
|
Output Parameters
|
|
|
|
|
Capacity
|
1kVA/800W
|
2kVA/1600W
|
3kVA/2400W
|
|
Power Factor
|
0.8
|
|
Nominal Voltage
|
220/230/240 Vac
|
|
Voltage THD
|
<3%- Linear Load <6%- Non Linear Load
|
<4%- Linear Load <7% - Non Linear Load
|
<4%- Linear Load <7%- Non Linear load
|
|
Frequency Regulation-Free Run (Unsynchronized with bypass)
|
+0.5 Hz
|
|
Frequency Regulation (Synchronized with bypass)
|
47.5-52.5 Hz/57.5-62.5 Hz
|
|
Creast Factor
|
3:1 max.
|
|
AC-AC Efficiency
|
88% R-Load, 87% RCD-Load
|
|
Transfer time-mains to battery
|
0 millisec
|
|
Transfer time â Inverter to bypass-Synchronization mode
|
4 msec.
|
|
Input Parameters
|
|
|
Configuration
|
1 phase, L-N+PE
|
|
Nominal Voltage
|
230 Vac
|
|
Voltage Range
|
160V to 300V at 100% Load, At 60% Load 110V to 300 Vac
|
|
Frequency
|
50/60 Hz
|
|
Frequency Range-Hz
|
40-70 Hz
|
|
Power Factor
|
>0.95
|
|
Battery Charger
|
|
|
Nominal Voltage-Float
|
41 Vdc
|
108 Vdc
|
82.1 Vdc
|
|
Maximum Charging Current-STD./LB.
|
1A-STD and 4/8A-LB
|
|
Battery Parameters
|
|
|
Type
|
SMF
|
|
No. of battery blocks (SB Model)
|
3x7 Ah
|
6x7 Ah
|
6x9 Ah
|
|
Battery Voltage (LB Model)
|
36 Vdc (3 Battery Blocks)
|
96 VDC ( Battery Blocks)
|
96 VDC (8 Battery Blocks)
|
|
Environmental Parameters
|
|
|
Operating Temperature
|
0 to 40 deg. Centigrade
|
|
Storage Temperature
|
-20 to 50 deg. Centigrade
|
|
Noise Level
|
<45db
|
|
Mechanical Parameters
|
|
|
Height x Width x Depth (mm)
|
220x145x388.5
|
318x190x387
|
318x190x387
|
|
Weight
|
13 kg.-STD., 7 kg.- LB
|
26 kg.- STD., 13 kg. - LB
|
28 kg.- STD., 13 kg. -LB
|
|
Colour/Panel Finish
|
RAL 7016 dark grey
|
|
Protection
|
IP20
|
|
Communication Port
|
RS232, USB
|
|
EPO (Emergency Power off Mode)
|
Yes
|
|
Monitoring software
|
SNMP, dry contact card, UP Silon 2000
|
|
Standards
|
|
|
EMI
|
EN 62040-2:2006
|
|
Safety
|
EN 62040-1-1:2003
|
|
Performance (Technical Feature)
|
IEC/EN 62040-3
|
|